Applications
The cables are multicore stranded flexible cables sheathed with thermoplastic LSZH compound. The cables have the ability to restrict the propagation of the flame in the event of a fire. This is especially important to slow down the spreading of the fire as the cables may pass from one area to another within a building. Applications can be found in control and power circuits, power stations, underground tunnels, lifts, escalators, and high-rise buildings.
Standards
Basic design |
BS 7629-1 |
Halogen Free |
IEC 60754-1 |
No corrosive gas emission |
IEC 60754-2 |
Minimum Smoke Emission |
IEC 61034-1/2 |
Reduced Fire Propagation |
IEC 60332-3C / NF C 32070-2.2 (C1) |
Flame Retardance |
IEC 60332-1 / NF C 32-070-2.1 (C2) |
Fire Resistance |
IEC 60331 / NF C 32070-2.3(CR1) |
VOLTAGE RATING
300/500V
Construction
Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2 or class 5.
Insulation: Mica glass tape covered by extruded cross-linked XLPE compound.
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1.
Dielectric test: |
2000 V r.m.s. x 5’ (core/core) |
Insulation resistance |
1000 MΩ x km (at 20°C) |
Short circuit temperature |
250°C |
Physical AND THERMAL PROPERTIES
Temperature range during operation (fixed state): -30°C – +90°C
Temperature range during installation (mobile state): -20°C – +50°C
Minimum bending radius: 8 × Overall Diameter
CONSTRUCTION PARAMETERS
FFX200 05mRZ1-R 6G0.5
FFX200 05mRZ1-F 6G0.5
No.of core |
Nominal |
Number & |
Nominal Insulation Thickness |
Nominal Sheath Thickness |
Nominal Overall Diameter |
Approx. Weight |
|
mm2 |
No/mm |
mm |
mm |
mm |
kg/km |
6 |
0.5 |
7/0.31 |
0.5 |
0.5 |
2.9 |
61 |
6 |
0.5 |
16/0.2 |
0.5 |
0.5 |
2.9 |
61 |